Frp tube with superior mechanical and electrical character FRP Tubes is used as insulating part in machinery and electrical instruments, FRP Tubes also can be used as pressure ,usually used in the transformer
Frp tube specification
It is suitable for mechanical & electrical applications, with good electrical properties in oil and under normal conditions;
Date sheet
Size : ID:10MM TO 600MM . Wall thickness :Min :1.5mm







Frp tube specification
It is suitable for mechanical & electrical applications, with good electrical properties in oil and under normal conditions;
Date sheet
No. | Item | Units | Value |
3520 | |||
1 | Applicable Standards | - | JB/T 3172-1999 |
2 | Density | g/cm³ | 1.03~1.20 |
3 | Bending strength perpendicular to laminations | MPa | 50 |
4 | Impact strength | MPa | 50 |
5 | Bonding strength | MPa | - |
6 | Voltage endurance parallel to lamination (in oil 90±2°C) | kV | 20 |
7 | Voltage endurance perpendicular to lamination (in oil 90 ±2°C) | kV/mm | 6.0 |
8 | Insulation resistance Impregnated in water | MΩ | - |
9 | Water absorption, wall thick 5mm | % | 6.0 |
10 | Temperature index | OC | 120 |
Size : ID:10MM TO 600MM . Wall thickness :Min :1.5mm