GF106T PORTABLE Current transformer test equipment



It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
MAIN FUNCTIONS
I. Current Transformer (CT)II. Voltage Transformer (PT)
PARAMETERS
Electrical parametersElectrical parameters - continuedStandardsMechanical parametersEnvironmental conditions



It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
MAIN FUNCTIONS
I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve | 1. Excitation characteristic test |
2. Transformation ratio test | 2. Transformation ratio test |
3. Polarity | 3. Polarity |
4. 5% and 10% error curve | 4. Withstand test of power frequency alternating current |
5. Current Injecting | 5. Degauss |
6. Degauss | 6. Calculation of knee point value |
7. Withstand test of power frequency alternating current | 7. Actual secondary load test |
8. Automatic calculation of excitation knee point value | 8. Resistance test |
9. Actual secondary load test | |
10. Resistance test |
PARAMETERS
Electrical parametersElectrical parameters - continuedStandardsMechanical parametersEnvironmental conditions
Accuracy | 0.2%, 0.5% | |
Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
Excitation voltage output | 0-2500Vrms, | |
Excitation current output | 0-5Arms (20A peak-value) | |
Large current output | 0-1000A | |
Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
Secondary winding DC resistance measurement | Range | 0.1-300Ω |
Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
Secondary actual load measurement | Range | 5VA-1000VA |
Accuracy | ≤0.5% (0.2%RD+0.3%RG)±0.1VA | |
CT/PT phase error measurement | Accuracy | ±4min |
Resolution | 0.01min | |
CT ratio error measurement | Range | ≤25000A/5A(5000A/1A) |
Accuracy | ≤0.5% | |
PT ratio error measurement | Range | 1-500KV |
Accuracy | ≤0.5% | |
Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012 | |
Safety standards | GB 4793.1-2007 | |
EMC | EMC standard 89/336/EEC | |
FCC Subpart B of Part 15 Class A | ||
IEC 1000-4-2 /3 /4 /6 | ||
Overall dimension (L x W x H) (mm) | 400 x 250 x 250 | |
Weight (kg) | ≤22 | |
Relative humidity | 90RH% | |
Operating temperature | -10°C to +40°C | |
Altitude | ≤1000m |