GDHL Series DC Loop Resistance Tester for Circuit Breaker


General Introduction:
GDHL Series High Voltage Switch Contact Resistance Tester is to test the contact resistance of circuit breaker or high current cable contacts.
GDHL Series High Voltage Switch Contact Resistance Tester is designed according to IEC62271. The main application of the tester is measurement of circuit breaker contact resistance.
All the test results of the tester could be print by the micro-printer which is integrated in the tester.
Also all the test results saved in the tester could be upload to PC computer and then convert to MS WORD document.
Functions and Technique Index:
Technique Index:


General Introduction:
GDHL Series High Voltage Switch Contact Resistance Tester is to test the contact resistance of circuit breaker or high current cable contacts.
GDHL Series High Voltage Switch Contact Resistance Tester is designed according to IEC62271. The main application of the tester is measurement of circuit breaker contact resistance.
All the test results of the tester could be print by the micro-printer which is integrated in the tester.
Also all the test results saved in the tester could be upload to PC computer and then convert to MS WORD document.
Functions and Technique Index:
1 Contact resistance measurement |
2 Result print |
3 Unload data to PC |
Technique Index:
1 | Measurement range: 0-1999.9 μ Ω Resolution: 0.1 μ Ω |
2 | Test current: DC 200A/100A for different selection |
3 | Maximum error< 0.5 %RDG+0.05%FS |
4 | Display mode: LCD |
5 | Save no more than 100 groups of data |
6 | RS232 computer interface |
7 | Rated power supply: AC220V |
8 | Size: 340 × 280 × 210mm3 |
9 | Environment temperature: -10 º C~+40º C Relative humidity<80% |
10 | Weight: <17kg |