TEST-901 LARGE CURRENT 1000A PRIMARY CURRENT INJECTION TEST SET
TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
The Primary Current Injection Set 1000A is a high current supply unit, which is very easy to move about because of its convenient modular design. The primary injection set 1000A is a compact instrument with a built-in ammeter, which meets the stringent requirements for accuracy, easy handling and performance
primary current injection test
primary current injection test procedure
primary current injection tester
primary injection test equipment
current injection test equipment
current injection testing
primary injection testing procedure
primary injection vs secondary injection
Some results are removed in response to a notice of local law requirement. For more information, please see here.
PARAMETERS
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply(AC) | 220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz |
Current Output (AC) | 1000A·5V or 500A·10V |
Capacity | 5KVA |
The current output waveform distortion | ≤5% |
Dual protection | overload electronic protection and software protection |
Primary current | |
Range | 0-1100A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
1000A range | 1000A 2-3minutes 500A 3-6minutes |
500A range | 500A 2-3minutes |
With timer | |
Range | 0.0001~999.99S |
Resolution | 0.001S |
Accuracy | <0.5%±5 words |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 430×260×260 |
Weight(kg) | 25 |
Environmental conditions | |
Temperature | -10°C to 40°C |
Relative humidity | ≤80% |
SELECTION GUIDE
Model | ACCU RACY | Primary current | AMMETER (0-6A) | TIMER | POWER | INJECTION CURRENT TIME | DIMENSION(W×D×H)(mm) | WEIGHT | REMARK |
---|---|---|---|---|---|---|---|---|---|
TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min | 430×260×260 | 25KG | Integrated structure |
TEST-902 | 0.5% | 0-2200A | YES | OPTIONAL | 12KVA | 2000A:2-3min; 1000A:3-6min | 360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
TEST-903 | 0.5% | 0-3300A | YES | OPTIONAL | 15KVA | 3000A:2-3min; 1500A:3-6min | 380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
TEST-905 | 0.5% | 0-5500A | YES | OPTIONAL | 25KVA | 5000A:2-3min; 2500A:3-6min | 430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |
Photo