Transformer Oil Automatic Dielectric Loss Tester

GDGY Transformer Oil Automatic Dielectric Loss Tester Introduction:GDGY type Transformer Oil Automatic Dielectric Loss Tester is dedicated to insulating oil liquid medium of dielectric loss angle and volume resistivity testing of high precision instruments. Specifications:Condition of Use-5&ord

Featured Products

GDGY Transformer Oil Automatic Dielectric Loss Tester

 

Introduction:
GDGY type Transformer Oil Automatic Dielectric Loss Tester is dedicated to insulating oil liquid medium of dielectric loss angle and volume resistivity testing of high precision instruments.

 

Specifications:

Condition of Use-5ºC-40ºC RH<80%
Power SourceAC 220V±10% Without Frequency Limit
AC High Voltage Output400V-2200V ±2% Every 100V 50VA
DC High Voltage Output00V-2200V ±2%
Temperature Control Induction StoveMaximal Power 500W
Temperature Control Range<100ºC
Temperature Measuring Error±0.5ºC
Control Temperature Error0.1ºC
Control Temperature TimeRoom Temperature 90ºC <20min

Measuring Range
tgδ Without Limit
Cx 15PF-300PF
Rx 10M-10T
Resolutiontgδ 0.001%
Cx 0.01pF
Rx 0.01
Precisiondelta tgδ:±(Reading*0.5%+0.020%)
delta Cx :±(Reading*0.5%+0.5PF)
delta Rx :±Reading * 10%
Relative Dielectric Loss ConstantΕr Calculated Automatically
Volume Resistivityρ Calculated Automatically
Dimension450(L)×310(W)×360(H)
Net Weight21KG

 

 

 

Features:

  • Light weight, small size, test safe operation, a complex dual-use, portable integrated structure.
  • With all-digital technology, the operation is intelligent and automatic;
  • With a large screen (240 * 180) LCD display;
  • Test results can be printed out;
  • Easy operation, the operators without professional training can be skilled use.
  • One heating part adopts the most advanced of the current high-frequency induction heating method, the heating oil-cup with non-contact with the heater, heating evenly, fast and convenient control and so on.
  • AC Test Power Supply with AC-DC-AC conversion means, effectively prevent the mains voltage and frequency fluctuations of the dielectric loss test the accuracy of the impact of even the generator, the instrument can also be run correctly.
  • Internal standard capacitors SF6 inflatable 3-pole capacitor, the capacitor dielectric loss and electrical capacity is not the ambient temperature, humidity, etc., to guarantee precision equipment in line even after prolonged use.
 

Internal Integration:

1Dielectric loss oil cup
2Temperature controller
3temperature sensor
4dielectric loss test bridge
5AC high voltage test power supply
6standard capacitors
7

High impedance meter

8DC high voltage test power supply and other major components

 

 

Contact us